300–2000 kg/h · up to 25 bar · hard coal and lignite
Full-cycle manufacturing — from incoming steel to the finished product.
Certified to TR CU 032/2013
*
TANSU supplies the steam boiler in the configuration needed for the equipment to work efficiently. The components come from carefully selected manufacturers whose quality has been proven by thirty years of practice.
Spirax Sarco
Automatic surface and bottom blowdown — Spirax Sarco, the leader of the steam and condensate systems industry. All Spirax Sarco components for boilers, boiler houses and industrial plants can be supplied.
Deaerator · condensate tank
We build them for your production duties — with automatic or manual control.
Any components — to your preference
Thanks to long-standing relationships with manufacturers we will supply any components you are used to — a burner of your usual brand, for example. The standard scope of supply does not limit your choice.
TR CU 032 certificate · Boiler passport · Operating manual with diagrams · Steel certificates · Seamless tube certificates · Independent laboratory report on the welded joints · Strength calculation.
In the TANSU fire-tube steam boiler the hot combustion products travel inside the smoke tubes, washed by water on every side, and give up their heat through the tube walls. Across three gas passes we reach the maximum heat recovery: efficiency up to 80 % on solid fuel. Every TANSU steam boiler is built to this scheme.
The three-pass scheme gives up to 80 % efficiency on solid fuel — a high figure for coal-fired boilers.
The water reserve in the shell holds steam pressure steady even under sharp peak loads.
Unlike European fire-tube counterparts, TANSU boilers are more tolerant of water chemistry regime upsets: a deviation in water treatment does not damage the boiler immediately and allows it to run for some time until the fault is corrected. This is a very significant operational advantage.
There is no power-hungry induced-draught fan — so no constant load on the electrical supply and no extra operating costs.
A monoblock steel construction with natural circulation: simple to service and long-lived.
The standard sizes are 500, 1000 and 2000 kg of steam per hour. Select a model to highlight its parameters. Boilers of other capacities and of intermediate outputs are built to order — the configuration is defined by the questionnaire.
| Model | E-0.5-0.9RN | E-1.0-0.9RN | E-2.0-0.9RN | |
|---|---|---|---|---|
| Steam output | kg/h | 500 | 1,000 | 2,000 |
| Useful heat output | kW | 335 | 670 | 1,350 |
| Efficiency at nominal output | % | 80 | 80 | 80 |
| Steam working pressure | bar | 8 | 8 | 8 |
| Steam temperature | °C | 175 | 175 | 175 |
| Furnace inner diameter | mm | 770 | 840 | 1,000 |
| Furnace length with the reversal chamber | mm | 2,500 | 2,800 | 3,600 |
| Furnace type | 3-pass | 3-pass | 3-pass | |
| Aerodynamic resistance | mbar | 2.0 | 2.5 | 6 |
| Flue diameter | mm | 300 | 400 | 600 |
| Steam line connection diameter | mm | 65 | 65 | 80 |
| Weight without water | kg | 3,350 | 4,900 | 8,200 |
| Boiler water volume | m³ | 2.3 | 3.37 | 6.1 |
| Boiler steam volume | m³ | 0.563 | 1.06 | 1.46 |
| Dimensions, mm | ||||
| Length | mm | 3,330 | 3,680 | 4,600 |
| Width | mm | 1,740 | 1,940 | 2,220 |
| Height | mm | 1,980 | 2,185 | 2,495 |
* All parameters are given for the nominal duty. 3-pass — straight-through (three-pass) furnace. Weight, volumes and dimensions are for reference; the final scope of supply is confirmed by the questionnaire.
Our own technical control department checks every operation — from incoming steel inspection to final testing. The QC department reports directly to the head of the company.
Raw material and welds are checked by an independent laboratory: visual and measuring inspection (VT) reveals surface defects, ultrasonic testing (UT) — hidden defects inside the weld.
From steel cutting to hydraulic testing of the equipment at our own production base — full control of every operation.
The equipment is manufactured in strict accordance with TR CU 032. Inspection control is carried out annually, with independent specialists attending.
YouTube · 16:9
Quality control, laboratory inspection and the full manufacturing cycle — in one film about the plant.
Plant tour — Russian narration; English subtitles available via CC.
TANSU steam boilers work wherever steam is part of the process.
…and any other production where process steam is required — the boiler is selected for the duty from the questionnaire.
TANSU is an export-oriented plant: deliveries go to every CIS country, above all Kazakhstan and Russia. In 31 years of work more than 2000 boilers have been built for enterprises in the food, oil and gas, paper, construction and other industries. Below are some of the customers of recent years.




























































































The products are certified and undergo annual independent inspection control. That guarantees consistent quality from batch to batch.
“On the safety of equipment operating under excess pressure”. The boilers are manufactured in strict accordance with the regulation and undergo annual independent inspection control.
EAEU certificate of conformity · TR CU 032
Certificate of Conformity TR CU 032/2013 — official document (Russian)
Fill in the short form — that is enough for a quick estimate. Need an exact calculation and a quotation? Expand the full questionnaire.